==Aluminium Anneal furnace (C4)==
==Aluminium Anneal furnace (C4)==

Revision as of 12:42, 11 October 2013

Feedback to this page: click here

Aluminium Anneal furnace (C4)

C4 Aluminium Anneal furnace. Positioned in cleanroom 2

The Aluminium Anneal furnace (C4) is a Tempress horizontal furnace for annealing of silicon wafers with aluminium.

This furnace is the lowest of the furnace tubes in the furnace C-stack positioned in cleanroom 2. In this furnace it is allowed to enter wafers that contain aluminium. Check the cross contamination chart.

The user manual, technical information and contact information can be found in LabManager:

Aluminium Anneal furnace (C4)

Process knowledge

Overview of the performance of Aluminium Anneal furnace and some process related parameters

Purpose Annealing Annealing of wafers containing aluminium.
Performance Film thickness
Process parameter range Process Temperature
  • 400-500 oC
Process pressure
  • 1 atm
Gas flows
  • N2: 5 sccm
  • O2: 5 sccm
Substrates Batch size
  • 1-30 4" wafer (or 2" wafers)
Substrate material allowed

Silicon wafers with alluminium. Wafers are allowed after alluminium lift off or after alluminium etch and resiststrip in acetone